Overview
Quick Details
Place of Origin:
Fujian, China (Mainland)
Brand Name:
Populace
Model Number:
704
Purpose:
brushless generator set
Weight:
0.35kg
Size:
18*12.5*3.5CM
Packing:
carton
Test temperature:
75 degree
Feature:
Automatic mains (utility) supply monitoring
Max current:
10AM
Operating Temperature Range:
-30 to +70°C
Power Supply:
8 to 35 Vdc Continuous
Guarantee:
365days
Packaging & Delivery
Packaging Details
Standard carton with Generator Controller 704 auto for start genset control from china
Delivery Time
with 2days after payment received

 Generator Controller 704 auto for start genset control from china


The DSE704 can be utilised as a Manual or Auto Start Module for single gen-set applications or engine only applications. The module has been designed to work with electronic and non-electronic engines, providing advanced engine monitoring and protection features.

*The Module 704 has been designed to monitor engine temperature, low oil pressure fail to start,

   charge failure, over speed and under speed. 

*Automatic mains (utility) supply monitoring 

*Automatic shutdown when fault conditions are detected 

*Manual start 

*Engine pre-heat 

*Engine monitoring and protection features 

*Protected solid state (PSS) outputs 

*Front panel mounting 

*Front panel programming 

*Remote start 

*LED indicators 

*Configurable timers 

*Configurable outputs 

*ransfers between mains (utility) and generator power 

* On-site module configuration to match user requirements 

* Multiple engine parameters are monitored simultaneously  

 

 

 

The DSE704 includes a back-lit icon LCD display which clearly shows the status of the engine at all times.

 

The module has been designed to combine a maximum of 16 generators and 16mains (utility)
supplies up to a maximum of 20 in one system, e.g. 16 generators and 4mains (utility) supplies (DSE5560 required to synchronise with the mains).

 

 

 Power Supply 8 to 35 Vdc Continuous
 Cranking Dropouts: Able to survive 0 V for 50 mS, providing supply was at least 10V
 Before dropout and supply recovers to 5V. 
 This is achieved without the need for internal batteries.
 Max Current Operating 50mA; Standby 10mA
 Alternator Input Range 75(ph-N) to 277(ph-N) 3 Phase 4wire AC (+20%)
 Alternator Input Frequency: 50 - 60 Hz at rated engine speed (Minimum: 75V AC Ph-N) (Crank
 Disconnect from 15V Ph-N @ 20Hz) Overspeed +14% (+24% overshoot)
 Underspeed –20%
 Start Output: 1.2 Amp DC at supply voltage
 Fuel Output: 1.2 Amp DC at supply voltage.
 Auxiliary Outputs 1.2 Amp DC at supply voltage
 Charge Fail 12V = 8V CF 24V = 16V CF
 Operating Temperature Range: -30 to +70°C

 

 

 

If you place a order from us,we will prepare the goods after recieving your bank slip. And will ship the goods to our shipping agent within 2 days once payment.Then it will take one week to delivery the goods.